Green Campus Initiative

Safe Sustainable Campus

Green Campus Initiative

Green Campus Initiative is an Environmental Health and Safety program to help reduce the energy footprint of the University as well as to improve safety and sustainability on campus. We are gathering preliminary data to assess the needs of the University. Our “2012 Shut the Sash” initiative reduced energy costs in the labs by approximately 43%.

Contacts:

 

Shut The Sash

Shut the Sash

What is it:

  • Many universities have programs to lower chemical fume hood (CFH) sash heights for sustainability and safety improvements. Wright State University joined the effort in 2012. The "Shut the Sash" team took measurements on air flow, sash heights, and baseline energy costs. With this information we were able to predict and to achieve significant energy cost reductions while promoting safe lab practices.

Who was involved:

  • 10 Buildings
  • 5 Departments
  • 61 Constant Air Volume fume hoods
  • 118 Variable Air Volume fume hoods

What was measured:

  • Sash Heights
  • Face Velocity (Air Flow)
  • Use Data (Is the fume hood in use or not?)

What Are The Benefits

Type Savings % Estimated Cumulative Annual Savings $
VAV 35% $75,000
CAV 38% $55,000

baseline_sash_height_chart.png

VAV vs. CAV

The two types of chemical fume hoods at Wright State are variable air volume (VAV) and constant air volume (CAV).

A "variable air volume" or VAV fume hood will maintain the speed (foot per minute) of the air into the fume hood regardless of sash height, but its air volume (cfm) will vary. The more open the sash, the more volume of air is needed. Since most of the air is conditioned, it must also be heated or cooled. Some studies have shown that up to 60% energy savings are possible. A true VAV system ties the fume hood exhaust with the room's air supply and exhaust.

A "constant air volume" or CAV does not adjust its air volume. The energy use and air volume (cfm) remain constant. The hood should be set up to have 80-120 fpm at 18" sash height. A lowered sash is the safest position for fume hood operations. A shut sash protects the laboratory worker from mishaps within the hood and possible hood failures.

A single CFH operating 24 hours per day uses about as much energy as 3 single family homes.

3_household_cfh.png

Safety Tips

Shut the Sash

  1. If you have a spill in a fume hood;
  2. If room ventilation goes down;
  3. If you leave your fume hood unattended;
  4. If an alarm sounds on the fume hood;
  5. If the air flow is flowing into the lab instead of into the fume hood.

Best Fume Hood Practices

  1. Use a fume hood for all chemical experiments if possible.
  2. Do not use the fume hood for chemical storage.
  3. Do not lean into the fume hood.
  4. When in use, keep the sash opening to a maximum of 18"
  5. Maintain 80-120 fpm face velocity during operation
  6. Always work in the hood with the sash opened only as much as possible.

shut_the_sash.png